Alarm Dispatch Module (ADM) Paging System

Alarm Dispatch Module (ADM) Paging System

  • 16 Dry Contact / Opto-Couples Inputs
  • TAP, SMS, KIRK and POCSAG Outputs
  • RS232/RS485 Connectivity to Fusion or PC
  • Multiple Recipients Per Alarm Input
  • TX and RX Indicator LEDs
  • Mains Powered Rack Mount Option

TERMINALS-008
Your Price $0.00
Qty
Product Information
Product Specifications
Related Literature

Suitable for Countless Applications

The Alarm Dispatch Module (ADM) provides 16 alarm inputs capable of taking data from various sources; from nursecall and building management systems to security and fire alarms. Connecting multiple ADMs via RS485 lets you expand the number of opto-coupled or dry contact inputs on your system - to provide the ideal messaging solution for your business. By connecting the ADM to Commtech Messenger, your business instantly has a means of tracking and analyzing data from all alarm events ever generated through the system.

TAP / SMS / DECT / POCSAG Capable

The ADM connects to an SMS service such as a wide area provider via dial-up modem using the TAP protocol. For SMS to cell phones, the ADM connects to its Fusion product-mate the Cellular Messaging Module. Connect a paging transmitter, such as the Fusion INTELPage and you instantly have a method of sending alarm messages to pagers.

PC Configurable

With a simple Windows® user interface, the configuration software is as easy to set up and configure as it is to use. Multilingual capabilities, plug and play unit setup and complete control over configuration help make getting connected as trouble-free as possible.

Advanced Input Settings

The Alarm Dispatch Module allows escalation paths to be configured for alarm events as well as latching of inputs and disabling of messaging inputs. By allowing pulsing, such as is commonly used in nurse call systems, the ADM effectively provides 32 inputs - initiating a different message when a pulsing signal is received.

Compliment Your System

Whether in stand-alone mode or as part of a larger Fusion system, the Alarm Dispatch Module provides reliable dispatch of alarm messages to the right people every time. Connecting the ADM to other modules in the versatile and durable Fusion range, gives you the ultimate in consumer-friendly messaging systems. 

  • Equipment Type
  • Alarm Dispatch Module

 

  • Languages Supported
  • English, Spanish, Mandarin, Dutch, German, French, Korean*

 

  • Alarm Capacity
  • 16 Alarm Inputs per Module

 

  • Power Supply
  • 110-240VAC 50/60Hz 25W max

 

  • External LED Indicators
  • Power, PTT, Data, RS485 TX, RS232 TX, RS232 RX, Alarm Input Status

 

  • External Connectors
  • Serial RS232: RJ45f x 2. Slave Only Port  |  POCSAG: RJ45fr with RS232 Level POCSAG Output  |  Alarm Inputs: Terminal Blocks

 

  • External Switches
  • Rotary Switches  |  Switch 1: RS485 Baud Rate  |  Switch 2 & 3: RS485 ID

 

  • Output Protocols
  • POCSAG, TAP [PET/IXO], SpectraLink, SMS, Kirk

 

  • Programming
  • Via Serial Cable [Required PC with ADM Configurator Software Installed]

 

  • Recipient Capacity
  • 8 x Addresses per Alarm Input [4 Initial, 4 Escalation]

 

  • Alarm Programming
  • Normally Open, Normally Closed, State Change, Disabled  |  Initial Delay: 65535 sec Max  |  Escalation Delay: 65535 sec Max  |  Escalation Repeats: 255 Max

 

  • Dimensions
  • [19" Rack Mount] 439x205x44 mm  |  17.3x8.1x1.7 inches [minus rack ears]

 

  • Dimensions 
  • [Plastic Desktop Enclosure] 73x216x254 mm  |  2.9x8.5x10 inches

 

  • Weight  
  • [19" Rack Mount] 2.7kg  |  5.9lb Net

 

  • Weight 
  • [Plastic Desktop Enclosure] 600g  |  1.3lb

 

  • Operating Temperature
  • 0°C to 50°C [32°F to 122°F] [20-95% RH Non-Condensing]

 

  • Storage Temperature
  • -10°C to 60°C [14°F to 140°F] [10-95% RH Non-Condensing]

 

  • Connection Capacity
  • Central - 39 ADM Units / 624 Inputs  |  CommtechMessenger - 39 ADM Units / 624 Inputs

 

  • Approvals
  • FCC / CE / C-tick / RoHS / IC / EN60950

 

  • *Call for your language addition

 

Alarm Dispatch Module Data Sheet  |  Download PDF
Alarm Dispatch Module User Manual - Plastic  |  Download PDF
Alarm Dispatch Module User Manual - Rack  |  Download PDF